ToU Mode

ToU Mode in Detail​

Try it now

Running Rules​

  • When the inverter's working mode is set to ToU mode but no time group is set, the inverter runs in General Mode, and the export power follows the external parameter (Inverter Configuration - Power Control - Export power).
  • If time groups are set, the export power set in the ToU sub-mode is used within those time groups; unset periods still run in General Mode, and the export power follows the external parameter (Inverter Configuration - Power Control - Export power).
  • When two time groups overlap or one fully contains the other, the overlapping period runs according to the setting with the earlier start time (i.e., first set, first effective). Avoid delivering overlapping time groups.
  • After an export power (exportLimit) is set in ToU mode, the external anti-reverse-current setting no longer takes effect; however, when external anti-reverse-current is enabled, output control (soft/hard) still takes effect.

Working Modes (workMode)​

The format is high byte#low byte:

ModeDescription
4#1General Mode
4#2Battery Force Charge
4#3Battery Charge
4#5Feed-in Priority
4#6Battery discharge

Time Group Fields​

There are 24 time groups per day (96 for 15-minute granularity) (timeGroupId: 0~23/95), and dates are distinguished by planId:

FieldDescriptionOptions/Range
planIdToU plan ID1: Today
2: Tomorrow
timeGroupIdToU time group ID, 24 in total0~23/95
timeGroupEnableFlagTime group enable flag0: Off
1: On
startTimeStart time00:00~23:59
endTimeEnd time00:00~23:59
workModeWorking modeSee "Working Modes"
parametersSub-mode parametersSee "Sub-mode Parameters"

Sub-mode Parameters (parameters)​

note

Parameter conversion (gain) is handled uniformly by the OpenAPI; when a parameter does not match the working mode, the mismatched parameter is filtered out directly.

ParameterDescriptionRangeUnit
exportLimitExport power[-1 × system rated power, 5 × system rated power]kW
chargeLimitCharge power limitSingle unit [0, 1000]
Master [0, 5000]
kW
chargeCutoffSocCharge cutoff SOC[100, 1000]%
noPvPV generation0: Allow PV generation
1: Disable PV generation
-
inverterOutputLimitInverter output controlSingle unit [0, 1000]
Master [0, 5500]
kW
dischargeCutoffSOCBattery discharge cutoff SOC[100, 1000]%

The parameters available under different working modes are as follows:

ParameterGeneral Mode 4#1Battery Force Charge 4#2Battery Charge 4#3Feed-in Priority 4#5Battery discharge 4#6
exportLimit✓✓✓✓✓
chargeLimit-✓✓--
chargeCutoffSoc-✓✓--
noPv-✓---
inverterOutputLimit----✓
dischargeCutoffSOC----✓

Delivery Rules​

  • Delivering a work plan is an asynchronous API: it returns a recordId on success, and you need to query the execution result via recordId.
  • ToU time groups must be delivered all 24/96 groups at once (one day's plan) and always overwrite the existing configuration on the device; for unused slots, set the enable flag (timeGroupEnableFlag) to 0 and send them as well.
  • Time groups have a today/tomorrow concept: if you want the device to keep working according to a set of ToU modes, deliver the data for both days (48/192 groups in total). The device automatically moves tomorrow's plan to today for execution at day rollover, in a continuous loop.
  • Time groups delivered via the Solinteg cloud platform (monitoring platform / OpenAPI platform) are cached in the cloud.
  • Delivery duration depends on the datalogger version: the first-generation datalogger (Duocom) takes about 1 minute, and the second-generation datalogger (R2MD) takes about 5 seconds. It is recommended to use ToU-related features together with the R2MD.
  • Tasks that time out (device not responding for a long time) will be marked as failed and can be retrieved via the result query API.

Reading the Current Configuration​

warning

Only the second-generation datalogger reports and supports reading the ToU configuration on the inverter; the first-generation datalogger does not. Therefore, when reading the configuration via the OpenAPI, the cloud-cached configuration is always returned.

Users of the first-generation datalogger please note: the cloud configuration is unreliable in this case and does not truly reflect the device's ToU configuration.

  • If ToU has never been set via the monitoring platform/OpenAPI, the query result is an empty array.
  • All APIs require authentication, and the current user must have operation permission on the device; otherwise a permission error is returned.
APIDescription
POST /tou/cmd/send/{deviceSn}Deliver an inverter work plan, returns a recordId
GET /tou/cmd/status/{taskId}Query the delivery result by recordId: SUCCESS / SETTING (processing) / FAILED
GET /tou/query/{deviceSn}Read the device's current ToU time groups (48/192 groups)