EMS Mode

EMS Mode in Detail​

Overview​

Under the EMS working modes, you can directly deliver control commands to control the inverter's behavior in real time:

  • EMS AC dispatch mode (3#1): directly control the inverter's AC port power;
  • EMS Battery dispatch mode (3#3): directly control the battery's charge/discharge power.

This mode has high requirements on network stability, and the control frequency is recommended to be once every 5~10 s; high-frequency control will accelerate chip wear on the hardware.

Delivery Method​

Control commands are delivered via the "running parameter configuration" API (POST /wrapper/cmd/set).

note

Some parameter keys have legacy names (e.g., singleTotalPowerDispatch, singlePhasePowerDispatchSettingA/B/C), which are deprecated. Use the new keys in this document.

EMS AC Dispatch Mode (3#1)​

Single-Unit System (the inverter's master-slave flag is single unit)​

KeyNameValid valuesUnitDescription
singleSysAcPowerDispatchModeSingle-unit AC power dispatch mode0 - Off
1 - Total power dispatch
2 - Independent three-phase power dispatch
-When 2 is selected, the three-phase unbalanced switch (gridConnectedUnbalancedSwitch) must be turned on
singleTotalDispatchPowerSingle-unit total power dispatch-kWEffective when dispatch mode = 1
Import power < 0; export power > 0
singleIndDispatchPhaseAPowerSingle-unit phase A power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0
singleIndDispatchPhaseBPowerSingle-unit phase B power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0
singleIndDispatchPhaseCPowerSingle-unit phase C power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0

Master-Slave Parallel System (the inverter's master-slave flag is master)​

KeyNameValid valuesUnitDescription
parallelSysScheduleModeParallel system dispatch mode0 - Master-slave automatic dispatch
1 - External EMS dispatch
2 - System dispatch off
-
parallelSysPowerModeSettingParallel system power dispatch mode setting0 - Off
1 - Total power dispatch
2 - Independent three-phase dispatch
-When 2 is selected, the three-phase unbalanced switch (gridConnectedUnbalancedSwitch) must be turned on
parallelSysTotalPowerSettingParallel system total power dispatch setting-kWEffective when dispatch mode = 1
Import power < 0; export power > 0
parallelSysPowerSettingAParallel system phase A power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0
parallelSysPowerSettingBParallel system phase B power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0
parallelSysPowerSettingCParallel system phase C power dispatch setting-kWEffective when dispatch mode = 2
Import power < 0; export power > 0

EMS Battery Dispatch Mode (3#3)​

Single-Unit System (the inverter's master-slave flag is single unit)​

KeyNameValid valuesUnitDescription
singleBatteryPowerDispatchSettingSingle-unit battery power dispatch setting-kWCharging < 0; discharging > 0

Master-Slave Parallel System (the inverter's master-slave flag is master)​

KeyNameValid valuesUnitDescription
parallelSysBatteryPowerSettingParallel system battery power dispatch setting-kWCharging < 0; discharging > 0

Application Scenarios​

EMS dispatch usually needs to be used together with the following export/import control parameters:

Control itemKeyRemarks
Export switchantiCounterCurrentStartStop
Export power limitgridSideMaxPowerLimit
Export power percentageantiReverseCurrentPowerSettingDeprecated
Import switchpeakLoadShiftSwitch
Import power limitgridMaximumCapacitySet

The following scenarios show the system behavior under different combinations of PV power, load power, and export/import limits (the battery dispatch power is the EMS Battery dispatch setting value):

ScenarioPV powerLoad powerExport switchExport power limitImport switchImport power limitBattery dispatch powerBattery powerGrid-side meter power
Scenario ①0kW5kWOn0On-10kW10kW (DisCharge)5kW0kW
Scenario ②3kW5kWOn0On-10kW10kW (DisCharge)2kW0kW
Scenario ③6kW5kWOn0On-10kW10kW (DisCharge)-1kW0kW
Scenario ④6kW5kWOn10kWOn-10kW10kW (DisCharge)9kW10kW (Export)
Scenario ⑤0kW5kWOn0kWOn-10kW-10kW (Charge)-5kW-10kW (Import)
Scenario ⑥6kW5kWOn0kWOn-10kW-10kW (Charge)-10kW-9kW (Import)

Sign convention: AC port power import (drawing power from the grid) < 0, export (feeding power to the grid) > 0; battery charging < 0, discharging > 0.