Inverter Configurations
Basic Parameters
| Setting Name | Setting Code | Value range | Unit | Read-only |
|---|---|---|---|---|
| Superior intelligent device SN (Smart Meter / DataLogger) | dataLoggerSN | When there is a physical connection between the inverter and the smart meter, the value is shown as the smart device's SN | ||
| Data reporting time for superior intelligent device | dataLoggerTime | |||
| Communication mode | communicationMode | Remote communication mode - Local communication mode When there is no local communication mode, "/" is displayed | Yes | |
| Rated power | standardPower | Yes | ||
| Firmware version | firmwareVersion | e.g. V1-0127-0053 0127 is the ARM version 0053 is the DSP version | Yes | |
| Master device SN (readonly) | masterSn | |||
| BMS SN (readonly) | masterControlSn | |||
| Safety regulation setting | safetyCountry | See appendix | ||
| Work mode setting | hybridWorkMode | See appendix | ||
| Grid type | outputModeSetting | 0 - Three-phase four-wire 1 - Three-phase three-wire | ||
| Battery protocol | batteryTypeCode | See appendix |
Basic Parameters / SOC Protection Settings
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| On-grid SOC protection | gridConnectedSocProtection | 1 - On 0 - Off | |
| On-grid discharge cut-off SOC | gridConnectedDischargeDepth | [10.0, 90.0] | % |
| Off-grid SOC protection | offGridSocProtection | 1 - On 0 - Off | |
| Off-grid discharge cut-off SOC | offGridDischargeDepth | [10.0, 90.0] | % |
Power Control
| Setting Name | Setting Code | Value range | Unit | Remark |
|---|---|---|---|---|
| Export Limit | antiCounterCurrentStartStop | 1 - On 0 - Off | ||
| Feed in Grid | antiReverseCurrentPowerSetting | [0.0, 100.0] | % | Please use Export to Grid instead. |
| Export to Grid | gridSideMaxPowerLimit | [-1 * standardPower, 5 * standardPower] | W | |
| Import limit | peakLoadShiftSwitch | 1 - On 0 - Off | ||
| Power from grid | gridMaximumCapacitySet | [0.0, 650.0] | kW | |
| Export Control | systemControl | 0 - Hard 1 - Soft | ||
| CT ratio setting | ctRatioSetting | [1, 6000] | ||
| Maximum output power | overloadModeSetting | 0 - Normal 1 - Overload 2 - UnderLoad |
Grid Connection Parameter
Grid Connection Parameter / Protection Parameters
The protection time gain is affected by the grid frequency. The gain is 0.05 at 50Hz and 0.06 at 60Hz (The purpose is to convert it to the frequency value (Prd) and store it on the device);
Please refer to the Safety Regulation List to query the grid frequency corresponding to the safety regulation
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| 10-min overvoltage protection switch | tenMinOverVoltageEnable | 1 - On 0 - Off | |
| 10-min overvoltage protection threshold | tenMinOverVoltageThreshold | [0.0,300.0] | V |
Grid Connection Parameter / Protection Parameters / OV/UV settings
To make it easier for customers to understand, the monitoring system converts Level-1 UV protection time, Level-1 OV protection time, Level-2 UV protection time, and Level-2 OV protection time. Customers send values in ms, and the monitoring system converts them to Prd before delivery.
| Setting Name | Setting Code | Value range | Unit | Description |
|---|---|---|---|---|
| Level-1 UV protection threshold | firstUnderVoltageValue | [0.0, 300.0] | V | |
| Level-1 UV protection time | firstUnderVoltageTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-1 OV protection threshold | firstOverVoltageValue | [0.0, 300.0] | V | |
| Level-1 OV protection time | firstOverVoltageTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-2 UV protection threshold | secondUnderVoltageValue | [0.0, 300.0] | V | |
| Level-2 UV protection time | secondUnderVoltageTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-2 OV protection threshold | secondOverVoltageValue | [0.0, 300.0] | V | |
| Level-2 OV protection time | secondOverVoltageTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
Grid Connection Parameter / Protection Parameters / OF/UF settings
| Setting Name | Setting Code | Value range | Unit | Description |
|---|---|---|---|---|
| Level-1 UF protection threshold | firstUnderFrequencyValue | [45.00, 65.00] | Hz | |
| Level-1 UF protection time | firstUnderFrequencyTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-1 OF protection threshold | firstOverFrequencyValue | [45.00, 65.00] | Hz | |
| Level-1 OF protection time | firstOverFrequencyTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-2 UF protection threshold | secondUnderFrequencyValue | [45.00, 65.00] | Hz | |
| Level-2 UF protection time | secondUnderFrequencyTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
| Level-2 OF protection threshold | secondOverFrequencyValue | [45.00, 65.00] | Hz | |
| Level-2 OF protection time | secondOverFrequencyTime | [1, 5000] | Prd | 50Hz:1prd=20ms ; 60Hz:1prd=16.67ms |
Grid Connection Parameter / Grid Connection Parameter
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Grid connection switch | reconnectionLimitEnable | 1 - On 0 - Off | s |
| Active power increase gradient | slowLoadRate | [0.0, 100.0] | %Pn/min |
Grid Connection Parameter / Grid Connection Parameter / Starting to generate power
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Lower voltage | voltageLowerThresholdForNoFault | [0.0, 300.0] | V |
| Upper voltage | voltageUpperThresholdForNoFault | [0.0, 300.0] | V |
| Lower frequency | frequencyLowerThresholdForNoFault | [45.00, 65.00] | Hz |
| Upper frequency | frequencyUpperThresholdForNoFault | [45.00, 65.00] | Hz |
| Observation time | waitingTimeForNoFault | [20, 1200] | s |
Grid Connection Parameter / Grid Connection Parameter / Reconnection after tripping
| Setting Name | Setting Code | Value range | Unit | Gain |
|---|---|---|---|---|
| Lower voltage | voltageLowerThresholdForFault | [0.0-300.0] | V | 10 |
| Upper voltage | voltageUpperThresholdForFault | [0.0, 300.0] | V | 10 |
| Lower frequency | frequencyLowerThresholdForFault | [45.00, 65.00] | Hz | 100 |
| Upper frequency | frequencyUpperThresholdForFault | [45.00, 65.00] | Hz | 100 |
| Observation time | waitingTimeForFault | [20, 1200] | s |
Grid Connection Parameter / Reactive Power Control
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Reactive Mode | reactivePowerControlMode | See appendix | |
| Power factor | pfPower | (-1.000, 1.000] | |
| Fixed Q | qparams | [-60.0, 60.0] | Pn% |
| PF curve at power point A | pfCurvePowerA | [0, 100.0] | % |
| PF curve at power point B | pfCurvePowerB | [20.0, 100.0] | % |
| PF curve at power point C | pfCurvePowerC | [20.0, 100.0] | % |
| PF curve at point A | pfPowerA | [0.800, 1.000] | |
| PF curve at point B | pfPowerB | [0.800, 1.000] | |
| PF curve at point C | pfPowerC | [0.800, 1.000] | |
| Q(U) Point 1 voltage | quVoltage1 | [184.0, 230.0] | V |
| Reactive power percent at point 1 | quReactive1 | [0.0, 60.0] | % |
| Q(U) Point 2 voltage | quVoltage2 | [184.0, 230.0] | V |
| Reactive power percent at point 2 | quReactive2 | [-60.0, 60.0] | % |
| Q(U) Point 3 voltage | quVoltage3 | [230.0, 276.0] | V |
| Reactive power percent at point 3 | quReactive3 | [-60.0, 60.0] | % |
| Q(U) Point 4 voltage | quVoltage4 | [230.0, 276.0] | V |
| Reactive power percent at point 4 | quReactive4 | [-60.0, 0.0] | % |
| Minimum cos(phi) | rsved28110 | [0.1, 0.8] | % |
| Time constant for Q(U) | timeConstant | [0.0, 60.0] | s |
| Lock in power | inQuPowerThreshold | [0.0, 100.0] | % |
| Lock out power | outQuPowerThreshold | [0.0, 100.0] | % |
Grid Connection Parameter / Voltage related active power P(U)
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| P(U) curve switch | overVoltageLoadReductionEnable | 1 - On 0 - Off | |
| P(U) curve start voltage | voltage3ForPuCurve | [230.0, 276.0] | V |
| Power of P(U) curve start voltage | power3ForPuCurve | [0.0, 100.0] | % |
| P(U) curve end voltage | voltage4ForPuCurve | [230.0, 276.0] | V |
| Power of P(U) curve end voltage | power4ForPuCurve | [0.0, 100.0] | % |
| P(U) Time constant (τ) | rsved28112 | [0.0, 60.0] | s |
Grid Connection Parameter / Active response to frequency deviation (FP)
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Overfrequency FP curve switch | overFrequencyLoadReductionEnableForFp | 1 - On 0 - Off | |
| Overfrequency threshold | overFrequencyLoadReductionStartFrequencyForFp | [50.00, 65.00] | Hz |
| Overfrequency threshold power | overFrequencyLoadReductionStartFrequencyPowerForFp | [0.0, 100.0] | % |
| Overfrequency end point frequency | overFrequencyLoadReductionEndFrequencyForFp | [50.00, 65.00] | Hz |
| Overfrequency end point power | overFrequencyLoadReductionEndFrequencyPowerForFp | [0.0, 100.0] | % |
| Overfrequency recovery threshold | recoveryPowerFrequencyThresholdForFpOverFrequencyLoadReduction | [50.00, 65.00] | Hz |
| Overfrequency deactivation time | powerRecoveryWaitingTimeForFpOverFrequencyLoadReduction | [0.800, 1.000] | s |
| Overfrequency power recovery rate | powerRecoverySlowLoadRateForFpOverFrequencyLoadReduction | [0.0, 100.0] | %/min |
Grid Connection Parameter / LVRT
- For voltage (V) related parameters below, when the monitoring system sends them to the inverter, they are multiplied by a coefficient and rounded before delivery. Therefore, when you read the values back from the device, there may be minor decimal differences compared to the values you originally sent.
- For example, if you set the Lock in voltage (Zero current) to 223.0V, the system sends it to the inverter as 223*22.624 = 5,045.152, which is rounded to 5,045. When reading back, 5,045/22.624 = 222.99, which rounds to 223.0V.
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| LVRT switch | lowThroughEnable | 1 - On 0 - Off | |
| Lock in voltage (Zero current) | lowThroughEntryVoltage | [11.5, 230] | V |
| Point 1 voltage | lowThroughVoltage1 | [11.5, 207] | V |
| Point 1 protection time | protectionTimeForLowThroughVoltage1 | [0, 62000] | ms |
| Point 2 voltage | lowThroughVoltage2 | [11.5, 207] | V |
| Point 2 protection time | protectionTimeForLowThroughVoltage2 | [0, 62000] | ms |
| Point 3 voltage | lowThroughVoltage3 | [11.5, 207] | V |
| Point 3 protection time | protectionTimeForLowThroughVoltage3 | [0, 62000] | ms |
| Point 4 voltage | lowThroughVoltage4 | [11.5, 207] | V |
| Point 4 protection time | protectionTimeForLowThroughVoltage4 | [0, 62000] | ms |
| Point 5 voltage | lowThroughVoltage5 | [11.5, 207] | V |
| Point 5 protection time | protectionTimeForLowThroughVoltage5 | [0, 62000] | ms |
Feature Parameters
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Multiple Inverter Role | masterSlaveFlag | 1 - Slave 2 - Master 0 - Independent | |
| On or Off-grid switch | allowParallelSwitch | 1 - On 0 - Off | |
| MPPT parallel connection | mpptParallelingSwitch | 1 - On 0 - Off | |
| Unbalanced Output | gridConnectedUnbalancedSwitch | 1 - On 0 - Off | |
| Off-grid overload reconnect delay | offGridOverload | [20, 1200] | s |
| Off-grid voltage setting | offGridVoltageSet | [195.5, 264.5] | V |
| N-PE check | npeCheckFlag | 1 - On 0 - Off | V |
Load Management
#x:takes the rated power of the device
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| DO(dry connector) Function Settings | do1Value | 0 - Disable 1 - External N-PE 2 - Load Management | |
| Load Management | loadControlMode | 0 - Off 1 - ManualMode 2 - SmartMode |
Load Management / Manual mode
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Switch Status | manualModeRelayStatus | 1 - On 0 - Off |
Load Management / Smart mode
| Setting Name | Setting Code | Value range | Unit |
|---|---|---|---|
| Feed-in Power Control or Battery SOC Control | controlTypeMode3 | 0 - All off 1 - Feed-in Power Control 2 - Battery SOC Control | |
| Feed-in Power Threshold | exportPowerThresholdMode3 | [0, #x] | W |
| Consumption Power Threshold | importPowerThresholdMode3 | [0, #x] | W |
| Start SOC Threshold | startSocMode3 | [0.00, 100.00] | % |
| End SOC Threshold | recoverySocMode3 | [0.00, 100.00] | % |
| Minimum Operation Hours | onceRunTimeMinMode3 | [0,120]&& less than Daily Max Operation Hours | min |
| Daily Max Operation Hours | oneDayRunTimeMaxMode3 | [1,1440]&& more than Minimum Operation Hours | min |
EV Charge Configuration
EV Charge configuration data is returned together with the configuration data of the inverter that the charger belongs to. Use the parent inverter's deviceSn for both control and configuration. Do not use the charger's own SN.
| Setting Name | Setting Code | Value range | Unit | Configuration or Control Method |
|---|---|---|---|---|
| Charger SN | chargerSN | - | - | Read-only |
| Charger device model | chargerDeviceType | e.g. ECA-S07K-BS0 ECA-S11K-BS0 ECA-S22K-BS0 | - | Read-only |
| Producer | chargerProducer | 0 - No producer 1 - Solinteg | - | Read-only |
| Firmware version | chargerFirmwareVersion | e.g. V01.00.03.01 | - | Read-only |
| Minimum charging power | chargerMinPower | [0.0, Rated charging power] | kW | Read-only |
| Rated charging power | chargerRatedPower | - | kW | Read-only |
| Gun type | chargerGunType | 1 - Single-phase AC gun 2 - Three-phase AC gun | - | Read-only |
| Charging mode | chargerRunMode | STOP - Stop charging FAST - Fast charging GREEN - Green charging SCHEDULE - Scheduled charging | - | Set charging mode |
| Maximum charging power limit | chargerMaxPower | Determined by charger device model chargerDeviceType ECA-S07K-BS0: [1.4, 7.0] ECA-S11K-BS0: [4.2, 11.0] ECA-S22K-BS0: [4.2, 22.0] | kW | Set device parameters |
| Main breaker current limit | chargerMainBreakerCurrentLimit | [6, 1000] | A | Set device parameters |
| Charger running strategy when inverter is abnormal | chargerInverterAbnormalStrategy | 0 - Standalone operation 1 - Inverter-controlled operation | - | Set device parameters |
| Independent running power when inverter is abnormal | chargerIndependentPower | [Minimum charging power, Rated charging power] | kW | Set device parameters |
| Independent charging control | chargerIndependentChargingControl | 0 - Idle 1 - Ready 2 - Start 3 - Stop | - | Start independent charging or Exit current charging mode |
| Time group 1 enable | chargerTimeGroup1Enable | 0 - Disabled 1 - Enabled | - | Set scheduled charging time groups |
| Time group 2 enable | chargerTimeGroup2Enable | 0 - Disabled 1 - Enabled | - | Set scheduled charging time groups |
| Time group 1 start time | chargerTimeGroup1StartTime | 00:00-23:59 | - | Set scheduled charging time groups |
| Time group 1 end time | chargerTimeGroup1EndTime | 00:00-23:59, earlier than the start time means crossing midnight | - | Set scheduled charging time groups |
| Time group 1 charging mode | chargerTimeGroup1ChargeMode | FAST - Fast charging GREEN - Green charging | - | Set scheduled charging time groups |
| Time group 2 start time | chargerTimeGroup2StartTime | 00:00-23:59 | - | Set scheduled charging time groups |
| Time group 2 end time | chargerTimeGroup2EndTime | 00:00-23:59, earlier than the start time means crossing midnight | - | Set scheduled charging time groups |
| Time group 2 charging mode | chargerTimeGroup2ChargeMode | FAST - Fast charging GREEN - Green charging | - | Set scheduled charging time groups |